Phone 220 180 780, E-mail: office@minib.cz
COIL – KO2
- universal convector, which also provides heat with the fan switched off
- high heat output
- COIL – KO2 is designed for heating of wet interiors especially where flooding is possible (heating of swimming pools)
DIMENSIONS
- total width
- 380 mm
- construction height
- 151 mm
- length
- 900 - 2500 mm
USAGE
COIL–KO2 is the universal convector suitable for use especially in wet spaces, where intensive flooding of the trough space occurs – e.g. swimming pools. The convector body is divided into 2 sections with a longitudinal partition. The narrower (empty) se- ction of the trough is used to collect most of the water coming into the convector from the swimming pool area thus protecting the wider section of the convector with the fan and heat exchanger from excessive flooding. Both longitudinal separated sections of the convector are fitted with drain pipes for the removal of the water from the bottom of the trough. The partition wall includes fall-over openings. The wider section of the trough with the fan and the heat exchanger is used for standard heating or partial cooling of the interior. The whole body of the unit is covered with an integral grille. The convector features high heat transfer levels when the fan is switched on but it also tempers the space when the fan is switched off. With 12V operation (AC motor) MINIB convectors are safe for applications in wet interiors as well. The convector cannot be installed to swimming pools with salt or other aggressive water. The convector is equipped with 12V AC motors; recommended control A1 or E1.
An example of connection and bridging of several convectors with a copper drain tube is shown on page no. 102.
TEMPERATURE EQUATION - HEATING
| m = 1,012688 | temperature exponent |
|---|---|
| tW, A | mean water temperature, mean air temperature [°C] |
| QN | nominal heat transfer rate for temperatures tW/tA 70/20 °C [W] |
| μ | μ = 1 (select μ according to the diagram for other than flow nominal values) |
| Q | heat transfer rate for other [W] |
HEAT TRANSFER RATE Q [W]
| length L = 900 mm | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| Fan speed and mean air temperature tA | |||||||||
| 1 - min. speed | 2 - med. speed | 3 - max. speed | |||||||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C |
| 90 °C | 1 341 | 1 251 | 1 215 | 1 465 | 1 366 | 1 327 | 1 634 | 1 524 | 1 480 |
| 70 °C | 980 | 890 | 854 | 1 070 | 972 | 933 | 1 194 | 1 084 | 1 040 |
| 60 °C | 800 | 710 | 674 | 874 | 775 | 736 | 974 | 865 | 821 |
| 45 °C | 530 | 441 | 405 | 579 | 482 | 443 | 646 | 537 | 494 |
| length L = 1000 mm | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| Fan speed and mean air temperature tA | |||||||||
| 1 - min. speed | 2 - med. speed | 3 - max. speed | |||||||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C |
| 90 °C | 1 565 | 1 459 | 1 417 | 1 710 | 1 594 | 1 548 | 1 906 | 1 778 | 1 726 |
| 70 °C | 1 143 | 1 038 | 996 | 1 249 | 1 134 | 1 088 | 1 392 | 1 264 | 1 213 |
| 60 °C | 933 | 828 | 786 | 1 019 | 905 | 859 | 1 136 | 1 009 | 958 |
| 45 °C | 619 | 514 | 473 | 676 | 562 | 516 | 754 | 627 | 576 |
| length L = 1250 mm | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| Fan speed and mean air temperature tA | |||||||||
| 1 - min. speed | 2 - med. speed | 3 - max. speed | |||||||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C |
| 90 °C | 2 124 | 1 981 | 1 923 | 2 320 | 2 164 | 2 101 | 2 587 | 2 413 | 2 343 |
| 70 °C | 1 551 | 1 409 | 1 352 | 1 695 | 1 539 | 1 476 | 1 890 | 1 716 | 1 646 |
| 60 °C | 1 266 | 1 124 | 1 067 | 1 383 | 1 228 | 1 165 | 1 542 | 1 369 | 1 300 |
| 45 °C | 840 | 698 | 642 | 917 | 763 | 701 | 1 023 | 850 | 782 |
| length L = 1500 mm | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| Fan speed and mean air temperature tA | |||||||||
| 1 - min. speed | 2 - med. speed | 3 - max. speed | |||||||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C |
| 90 °C | 2 683 | 2 502 | 2 430 | 2 931 | 2 733 | 2 654 | 3 268 | 3 047 | 2 959 |
| 70 °C | 1 960 | 1 779 | 1 707 | 2 141 | 1 944 | 1 865 | 2 387 | 2 167 | 2 080 |
| 60 °C | 1 599 | 1 420 | 1 348 | 1 747 | 1 551 | 1 472 | 1 948 | 1 729 | 1 642 |
| 45 °C | 1 061 | 882 | 811 | 1 159 | 963 | 885 | 1 292 | 1 074 | 987 |
| length L = 1750 mm | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| Fan speed and mean air temperature tA | |||||||||
| 1 - min. speed | 2 - med. speed | 3 - max. speed | |||||||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C |
| 90 °C | 3 242 | 3 023 | 2 936 | 3 541 | 3 302 | 3 207 | 3 949 | 3 682 | 3 576 |
| 70 °C | 2 368 | 2 150 | 2 063 | 2 587 | 2 349 | 2 254 | 2 884 | 2 619 | 2 513 |
| 60 °C | 1 933 | 1 715 | 1 628 | 2 111 | 1 874 | 1 779 | 2 354 | 2 089 | 1 984 |
| 45 °C | 1 282 | 1 066 | 979 | 1 400 | 1 164 | 1 070 | 1 561 | 1 298 | 1 193 |
| length L = 2000 mm | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| Fan speed and mean air temperature tA | |||||||||
| 1 - min. speed | 2 - med. speed | 3 - max. speed | |||||||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C |
| 90 °C | 3 801 | 3 544 | 3 442 | 4 152 | 3 872 | 3 760 | 4 630 | 4 317 | 4 192 |
| 70 °C | 2 776 | 2 521 | 2 419 | 3 033 | 2 754 | 2 642 | 3 382 | 3 071 | 2 946 |
| 60 °C | 2 266 | 2 011 | 1 909 | 2 475 | 2 197 | 2 085 | 2 760 | 2 450 | 2 326 |
| 45 °C | 1 503 | 1 249 | 1 148 | 1 641 | 1 365 | 1 254 | 1 830 | 1 522 | 1 399 |
| length L = 2500 mm | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| Fan speed and mean air temperature tA | |||||||||
| 1 - min. speed | 2 - med. speed | 3 - max. speed | |||||||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C |
| 90 °C | 4 919 | 4 587 | 4 454 | 5 373 | 5 010 | 4 865 | 5 991 | 5 587 | 5 425 |
| 70 °C | 3 593 | 3 262 | 3 130 | 3 925 | 3 563 | 3 419 | 4 376 | 3 974 | 3 813 |
| 60 °C | 2 932 | 2 602 | 2 471 | 3 203 | 2 843 | 2 699 | 3 572 | 3 170 | 3 010 |
| 45 °C | 1 945 | 1 617 | 1 486 | 2 124 | 1 766 | 1 623 | 2 369 | 1 969 | 1 810 |
Electric input for fans AC
| length | power input |
|---|---|
| 900 | 32 VA |
| 1000 | 37 VA |
| 1250 | 37 VA |
| 1500 | 64 VA |
| 1750 | 74 VA |
| 2000 | 74 VA |
| 2500 | 106 VA |
Search
Video
Assembly instructions
for floor convectors
play video »
Assembly instructions
for standing convectors
play video »
Management of quality
Since the year 2007 we have got the Certificate of Management of Quality for ISO 9001:2001 for the field of activity – manufacture of heating convectors.
EC Declaration of Conformity
All our listed products meet general requirements according to Statutory Rules no. 190/2002 Sb.