Phone 220 180 780, E-mail: office@minib.cz
COIL – KT110
- for heating dry interiors
- high heat output
- also heating when the fan is switched off
- KT110 variant with lower demands on construction height.
DIMENSIONS
- total width
- 303 mm
- construction height
- 110 mm
- length
- 900 - 3000 mm
USAGE
The most universal MINIB convector for dry applications. The convector produces high levels of heat output with the 12V fan switched on but it also heats – tempers the interior when the fan is switched off. A high heat output and ability to keep low levels of natural convection when the fan is switched off provide a wide range of uses for interiors with a variety of safety and heating demands.
TEMPERATURE EQUATION - HEATING
| m = 1,0543 | temperature exponent |
|---|---|
| tW, A | mean water temperature, mean air temperature [°C] |
| QN | nominal heat transfer rate for temperatures tW/tA 70/20 °C [W] |
| μ | μ = 1 (select μ according to the diagram for other than flow nominal values) |
| Q | heat transfer rate for other [W] |
HEAT TRANSFER RATE Q [W]
| length L = 900 mm | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| Fan speed and mean air temperature tA | |||||||||
| 1 - min. speed | 2 - med. speed | 3 - max. speed | |||||||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C |
| 90 °C | 1 114 | 1 036 | 1 005 | 1 220 | 1 134 | 1 100 | 1 374 | 1 278 | 1 239 |
| 70 °C | 804 | 727 | 696 | 880 | 796 | 762 | 991 | 896 | 858 |
| 60 °C | 650 | 574 | 544 | 712 | 629 | 596 | 802 | 708 | 671 |
| 45 °C | 424 | 350 | 320 | 464 | 383 | 351 | 523 | 432 | 395 |
| length L = 1000 mm | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| Fan speed and mean air temperature tA | |||||||||
| 1 - min. speed | 2 - med. speed | 3 - max. speed | |||||||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C |
| 90 °C | 1 300 | 1 209 | 1 172 | 1 423 | 1 324 | 1 284 | 1 603 | 1 491 | 1 446 |
| 70 °C | 937 | 848 | 812 | 1 026 | 928 | 889 | 1 156 | 1 046 | 1 002 |
| 60 °C | 759 | 670 | 635 | 831 | 734 | 695 | 936 | 826 | 783 |
| 45 °C | 495 | 408 | 374 | 542 | 447 | 409 | 610 | 503 | 461 |
| length L = 1250 mm | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| Fan speed and mean air temperature tA | |||||||||
| 1 - min. speed | 2 - med. speed | 3 - max. speed | |||||||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C |
| 90 °C | 1 764 | 1 641 | 1 591 | 1 932 | 1 796 | 1 742 | 2 176 | 2 023 | 1 962 |
| 70 °C | 1 272 | 1 151 | 1 102 | 1 393 | 1 260 | 1 207 | 1 569 | 1 419 | 1 359 |
| 60 °C | 1 030 | 909 | 862 | 1 127 | 996 | 943 | 1 270 | 1 122 | 1 062 |
| 45 °C | 671 | 554 | 507 | 735 | 607 | 556 | 828 | 683 | 626 |
| length L = 1500 mm | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| Fan speed and mean air temperature tA | |||||||||
| 1 - min. speed | 2 - med. speed | 3 - max. speed | |||||||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C |
| 90 °C | 2 229 | 2 072 | 2 010 | 2 440 | 2 269 | 2 201 | 2 748 | 2 556 | 2 479 |
| 70 °C | 1 607 | 1 453 | 1 392 | 1 760 | 1 591 | 1 524 | 1 982 | 1 792 | 1 717 |
| 60 °C | 1 301 | 1 149 | 1 088 | 1 424 | 1 258 | 1 192 | 1 604 | 1 417 | 1 342 |
| 45 °C | 848 | 700 | 641 | 929 | 766 | 702 | 1 046 | 863 | 790 |
| length L = 1750 mm | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| Fan speed and mean air temperature tA | |||||||||
| 1 - min. speed | 2 - med. speed | 3 - max. speed | |||||||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C |
| 90 °C | 2 693 | 2 504 | 2 429 | 2 949 | 2 742 | 2 659 | 3 321 | 3 088 | 2 995 |
| 70 °C | 1 942 | 1 756 | 1 682 | 2 126 | 1 923 | 1 842 | 2 395 | 2 166 | 2 075 |
| 60 °C | 1 572 | 1 388 | 1 315 | 1 721 | 1 520 | 1 440 | 1 938 | 1 712 | 1 622 |
| 45 °C | 1 025 | 846 | 774 | 1 122 | 926 | 848 | 1 264 | 1 043 | 955 |
| length L = 2000 mm | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| Fan speed and mean air temperature tA | |||||||||
| 1 - min. speed | 2 - med. speed | 3 - max. speed | |||||||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C |
| 90 °C | 3 157 | 2 936 | 2 847 | 3 457 | 3 214 | 3 118 | 3 894 | 3 620 | 3 511 |
| 70 °C | 2 277 | 2 059 | 1 972 | 2 493 | 2 254 | 2 159 | 2 808 | 2 539 | 2 432 |
| 60 °C | 1 843 | 1 627 | 1 542 | 2 017 | 1 782 | 1 688 | 2 272 | 2 007 | 1 901 |
| 45 °C | 1 202 | 991 | 908 | 1 316 | 1 086 | 994 | 1 482 | 1 223 | 1 120 |
| length L = 2500 mm | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| Fan speed and mean air temperature tA | |||||||||
| 1 - min. speed | 2 - med. speed | 3 - max. speed | |||||||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C |
| 90 °C | 4 086 | 3 799 | 3 685 | 4 474 | 4 160 | 4 035 | 5 039 | 4 685 | 4 544 |
| 70 °C | 2 946 | 2 665 | 2 552 | 3 226 | 2 917 | 2 795 | 3 633 | 3 286 | 3 148 |
| 60 °C | 2 384 | 2 106 | 1 995 | 2 611 | 2 306 | 2 184 | 2 941 | 2 597 | 2 460 |
| 45 °C | 1 555 | 1 283 | 1 175 | 1 703 | 1 405 | 1 287 | 1 918 | 1 582 | 1 449 |
| length L = 3000 mm | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| Fan speed and mean air temperature tA | |||||||||
| 1 - min. speed | 2 - med. speed | 3 - max. speed | |||||||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C | 15 °C | 20 °C | 22 °C |
| 90 °C | 5 014 | 4 663 | 4 522 | 5 490 | 5 105 | 4 951 | 6 184 | 5 750 | 5 577 |
| 70 °C | 3 616 | 3 270 | 3 132 | 3 959 | 3 581 | 3 430 | 4 459 | 4 033 | 3 863 |
| 60 °C | 2 926 | 2 585 | 2 449 | 3 204 | 2 830 | 2 681 | 3 609 | 3 187 | 3 020 |
| 45 °C | 1 908 | 1 575 | 1 442 | 2 090 | 1 724 | 1 579 | 2 354 | 1 942 | 1 779 |
Electric input for fans DC
| length | power input |
|---|---|
| 900 | 12 VA |
| 1000 | 12 VA |
| 1250 | 24 VA |
| 1500 | 24 VA |
| 1750 | 24 VA |
| 2000 | 36 VA |
| 2500 | 48 VA |
| 3000 | 48 VA |
Search
Video
Assembly instructions
for floor convectors
play video »
Assembly instructions
for standing convectors
play video »
Management of quality
Since the year 2007 we have got the Certificate of Management of Quality for ISO 9001:2001 for the field of activity – manufacture of heating convectors.
EC Declaration of Conformity
All our listed products meet general requirements according to Statutory Rules no. 190/2002 Sb.