Mo

CROSS SECTION

Mo

LONGITUDINAL SECTION

Mo
Download-in-pdf-icon Download-reader-icon

COIL – MO

  • very powerful MINIB floor convector
  • heating of any interior (in winter) and interior cooling (in summer) with the possibility of moisture condensation in the trough
  • heating of swimming pools
  • implied condensate outlet

DIMENSIONS

total width
303 mm
construction height
125 mm
length
900 - 3000 mm

USAGE

Convector COIL – MO is used as a fast reacting heating unit suitable for heating of interiors with high heat loads. Convector COIL – MO is also suitable for use in wet spaces, where pooling of water in the trench can occur. The convector has a specially profiled base enabling draining of collected water (eventually condensed water) through the outlet pipe at the bottom of the trough. The fan operates at the safe voltage of 12V (AC motor). If there is a source of chilled water (6/12 oC) available the COIL-MO may also be used for cooling of the interior. The convector will cause formation of cool air curtain by the window where it prevents room heating through convection from heated window surfaces. The cooling effect is most evident especially in the vicinity of windows so that the interior air is not fully cooled as in case of when using standard air conditioning. The convector cannot be installed to swimming pools with salt or other aggressive water. The convector is equipped with 12V AC motors; recommended control A1 or E1.

An example of connection and bridging of several convectors with a copper drain tube is shown on page no. 102.


TEMPERATURE EQUATION - HEATING

Q = μ QN
(
tW-tA 50
)
m
m = 1,0435 temperature exponent
tW, A mean water temperature, mean air temperature [°C]
QN nominal heat transfer rate for temperatures tW/tA 70/20 °C [W]
μ μ = 1 (select μ according to the diagram for other than flow nominal values)
Q heat transfer rate for other [W]

HEAT TRANSFER RATE Q [W]

°C
°C
°C
°C
length L = 900 mm
Fan speed and mean air temperature tA
1 - min. speed 2 - med. speed 3 - max. speed
Mean water temperature tW 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C
90 °C 1 740 1 620 1 571 1 824 1 698 1 647 1 995 1 856 1 801
70 °C 1 259 1 140 1 092 1 320 1 195 1 145 1 443 1 307 1 252
60 °C 1 021 903 856 1 071 947 897 1 170 1 035 981
45 °C 669 553 507 701 580 531 767 634 581
length L = 1000 mm
Fan speed and mean air temperature tA
1 - min. speed 2 - med. speed 3 - max. speed
Mean water temperature tW 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C
90 °C 2 030 1 889 1 833 2 128 1 981 1 922 2 327 2 165 2 101
70 °C 1 469 1 330 1 275 1 540 1 394 1 336 1 684 1 524 1 461
60 °C 1 192 1 054 999 1 249 1 105 1 047 1 366 1 208 1 145
45 °C 780 645 591 818 676 620 894 739 678
length L = 1250 mm
Fan speed and mean air temperature tA
1 - min. speed 2 - med. speed 3 - max. speed
Mean water temperature tW 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C
90 °C 2 756 2 564 2 488 2 889 2 688 2 608 3 158 2 939 2 851
70 °C 1 994 1 805 1 730 2 090 1 892 1 813 2 285 2 069 1 982
60 °C 1 617 1 430 1 356 1 695 1 499 1 421 1 853 1 639 1 553
45 °C 1 059 876 803 1 110 918 841 1 214 1 004 920
length L = 1500 mm
Fan speed and mean air temperature tA
1 - min. speed 2 - med. speed 3 - max. speed
Mean water temperature tW 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C
90 °C 3 481 3 239 3 143 3 649 3 395 3 294 3 989 3 712 3 602
70 °C 2 518 2 280 2 185 2 640 2 390 2 290 2 886 2 613 2 504
60 °C 2 043 1 806 1 712 2 141 1 894 1 795 2 341 2 070 1 962
45 °C 1 338 1 106 1 014 1 402 1 160 1 063 1 533 1 268 1 162
length L = 1750 mm
Fan speed and mean air temperature tA
1 - min. speed 2 - med. speed 3 - max. speed
Mean water temperature tW 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C
90 °C 4 206 3 914 3 797 4 409 4 103 3 980 4 820 4 485 4 352
70 °C 3 043 2 755 2 640 3 190 2 888 2 767 3 488 3 157 3 026
60 °C 2 468 2 183 2 069 2 587 2 288 2 169 2 829 2 502 2 371
45 °C 1 617 1 337 1 225 1 695 1 401 1 284 1 853 1 532 1 404
length L = 2000 mm
Fan speed and mean air temperature tA
1 - min. speed 2 - med. speed 3 - max. speed
Mean water temperature tW 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C
90 °C 4 931 4 589 4 452 5 169 4 810 4 667 5 651 5 259 5 102
70 °C 3 568 3 230 3 095 3 740 3 386 3 245 4 089 3 702 3 547
60 °C 2 894 2 559 2 426 3 033 2 683 2 543 3 316 2 933 2 780
45 °C 1 895 1 567 1 436 1 987 1 643 1 506 2 172 1 796 1 646
length L = 2500 mm
Fan speed and mean air temperature tA
1 - min. speed 2 - med. speed 3 - max. speed
Mean water temperature tW 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C
90 °C 6 382 5 938 5 761 6 689 6 225 6 039 7 314 6 806 6 603
70 °C 4 617 4 180 4 006 4 840 4 382 4 199 5 291 4 791 4 591
60 °C 3 745 3 312 3 139 3 925 3 471 3 291 4 292 3 795 3 598
45 °C 2 453 2 028 1 859 2 571 2 126 1 949 2 811 2 324 2 130
length L = 3000 mm
Fan speed and mean air temperature tA
1 - min. speed 2 - med. speed 3 - max. speed
Mean water temperature tW 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C
90 °C 7 832 7 288 7 071 8 210 7 640 7 412 8 976 8 352 8 103
70 °C 5 666 5 130 4 916 5 940 5 378 5 153 6 494 5 879 5 634
60 °C 4 596 4 064 3 853 4 818 4 260 4 038 5 267 4 658 4 415
45 °C 3 010 2 489 2 281 3 156 2 609 2 391 3 450 2 852 2 615

Electric input for fans AC

length power input
900 32 VA
1000 37 VA
1250 37 VA
1500 64 VA
1750 74 VA
2000 74 VA
2500 106 VA
3000 111 VA

Search

News

Catalogue

New catalogue MINIB 2010/2011
Download our new catalogue for the year 2010/2011!



Video

Video

Assembly instructions
for floor convectors
play video »

Assembly instructions
for standing convectors
play video »


Management of quality

En-small

Since the year 2007 we have got the Certificate of Management of Quality for ISO 9001:2001 for the field of activity – manufacture of heating convectors.


EC Declaration of Conformity

Confirmity

All our listed products meet general requirements according to Statutory Rules no. 190/2002 Sb.