Mt2

CROSS SECTION

Mt2

LONGITUDINAL SECTION

Mt2
Download-in-pdf-icon Download-reader-icon

COIL – MT2

  • the most universal MINIB convector
  • automatic angle of airflow
  • heating of dry and wet interiors
  • automatic blowing to window surfaces for demisting
  • partial cooling of the space in the summer
  • use possible only with the MT 2 control

DIMENSIONS

total width
380 mm
construction height
140 mm
length
900 - 2000 mm

USAGE

This convector includes 12 V DC motors with an extremely low power consumption and economical heating is ensured during operation. It uses the newly developed electronic IQ controller MINIB MT-2. This controller includes automatic continuous speed control of the fan (thus the heat output of the convector) via a microprocessor, automatic angle of airflow, user adjustable max. speed level, night speed reduction, user selection of the operation mode, disabling of fan at low water temperature and contactless, noiseless switching of the thermostat. The multifunctional convector enables automatic inclination of airflow with an extremely high heat output at very low speed. (At temperatures of 75/65/20 ºC, the convector achieves a heat output of approx. 1600 W for 1m length at medium speed.). The inclination of the warm airflow to different directions provides (based on the pulse from the sensor) either automatic demisting of steamed up windows by warm air from the convector or intensive heating of objects in the room into the interior by declined airflow. In standard mode, the convector generates the vertical heat curtain providing either heating of the interior or demisting of the window. Thanks to an arrangement of fans the convector can be used for cooling of the space in the summer as the cool air is directed into the room at an angle and not vertically. The fast-acting heat exchanger reacts very quickly to changing requirements and provides user‘s optimum levels of comfort.


TEMPERATURE EQUATION - HEATING

Q = μ QN
(
tW-tA 50
)
m
m = 1,080071 temperature exponent
tW, A mean water temperature, mean air temperature [°C]
QN nominal heat transfer rate for temperatures tW/tA 70/20 °C [W]
μ μ = 1 (select μ according to the diagram for other than flow nominal values)
Q heat transfer rate for other [W]

HEAT TRANSFER RATE Q [W]

°C
°C
°C
°C
length L = 900 mm
Fan speed and mean air temperature tA
1 - min. speed 2 - med. speed 3 - max. speed
Mean water temperature tW 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C
90 °C 1 983 1 841 1 784 2 134 1 980 1 919 2 392 2 220 2 152
70 °C 1 418 1 280 1 225 1 526 1 377 1 318 1 711 1 544 1 477
60 °C 1 142 1 006 951 1 229 1 082 1 024 1 378 1 213 1 148
45 °C 737 605 553 793 651 595 889 730 667
length L = 1000 mm
Fan speed and mean air temperature tA
1 - min. speed 2 - med. speed 3 - max. speed
Mean water temperature tW 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C
90 °C 2 313 2 147 2 081 2 489 2 310 2 239 2 791 2 591 2 511
70 °C 1 655 1 493 1 429 1 781 1 606 1 537 1 997 1 801 1 724
60 °C 1 332 1 173 1 110 1 434 1 262 1 194 1 607 1 415 1 339
45 °C 860 706 645 925 760 694 1 037 852 779
length L = 1250 mm
Fan speed and mean air temperature tA
1 - min. speed 2 - med. speed 3 - max. speed
Mean water temperature tW 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C
90 °C 3 140 2 914 2 824 3 378 3 135 3 039 3 788 3 516 3 407
70 °C 2 246 2 026 1 939 2 416 2 180 2 086 2 710 2 445 2 339
60 °C 1 808 1 592 1 506 1 946 1 713 1 621 2 182 1 921 1 817
45 °C 1 167 958 876 1 256 1 031 942 1 408 1 156 1 057
length L = 1500 mm
Fan speed and mean air temperature tA
1 - min. speed 2 - med. speed 3 - max. speed
Mean water temperature tW 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C
90 °C 3 966 3 681 3 568 4 267 3 961 3 839 4 785 4 441 4 304
70 °C 2 837 2 559 2 449 3 052 2 754 2 635 3 423 3 088 2 955
60 °C 2 284 2 011 1 903 2 458 2 164 2 047 2 756 2 426 2 296
45 °C 1 474 1 211 1 106 1 586 1 303 1 190 1 778 1 461 1 335
length L = 1750 mm
Fan speed and mean air temperature tA
1 - min. speed 2 - med. speed 3 - max. speed
Mean water temperature tW 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C
90 °C 4 792 4 448 4 311 5 156 4 786 4 638 5 781 5 366 5 201
70 °C 3 428 3 093 2 959 3 688 3 328 3 184 4 136 3 731 3 570
60 °C 2 760 2 430 2 299 2 970 2 615 2 474 3 330 2 932 2 774
45 °C 1 781 1 463 1 337 1 916 1 574 1 438 2 149 1 765 1 613
length L = 2000 mm
Fan speed and mean air temperature tA
1 - min. speed 2 - med. speed 3 - max. speed
Mean water temperature tW 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C
90 °C 5 618 5 215 5 054 6 045 5 611 5 438 6 778 6 291 6 097
70 °C 4 019 3 626 3 469 4 324 3 901 3 733 4 849 4 374 4 186
60 °C 3 236 2 849 2 696 3 482 3 066 2 900 3 904 3 438 3 252
45 °C 2 088 1 715 1 567 2 247 1 845 1 686 2 519 2 069 1 891

Search

News

Catalogue

New catalogue MINIB 2010/2011
Download our new catalogue for the year 2010/2011!



Video

Video

Assembly instructions
for floor convectors
play video »

Assembly instructions
for standing convectors
play video »


Management of quality

En-small

Since the year 2007 we have got the Certificate of Management of Quality for ISO 9001:2001 for the field of activity – manufacture of heating convectors.


EC Declaration of Conformity

Confirmity

All our listed products meet general requirements according to Statutory Rules no. 190/2002 Sb.