Coil-kz

CROSS SECTION

Coil-kz-pricny

LONGITUDINAL SECTION

Coil-kz-podelny
Download-in-pdf-icon Download-reader-icon

COIL – KZ 60

  • fan assisted convector
  • built-in convector designed for installation into the wall
  • heating of dry interiors

DIMENSIONS

construction height
360 mm
length
900 - 2000 mm
hloubka
60 mm

USAGE

The convector KZ is a fast reacting heater whose advan- tage is its small built-in depth in variants of 60 mm and 90 mm. The heater is supplied as standard with a woo- den or stainless visible panel that meets high aesthetic requirements.

   


TEMPERATURE EQUATION - HEATING

Q = μ QN
(
tW-tA 50
)
m
m = 1,0654 temperature exponent
tW, A mean water temperature, mean air temperature [°C]
QN nominal heat transfer rate for temperatures tW/tA 70/20 °C [W]
μ μ = 1 (select μ according to the diagram for other than flow nominal values)
Q heat transfer rate for other [W]

HEAT TRANSFER RATE Q [W]

°C
°C
°C
°C
length L = 900 mm
Fan speed and mean air temperature tA
1 - min. speed 2 - med. speed 3 - max. speed
Mean water temperature tW 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C
90 °C 680 632 613 804 747 724 1 045 971 941
70 °C 489 442 423 578 522 500 751 678 649
60 °C 395 348 330 467 412 390 606 535 506
45 °C 256 211 193 303 249 228 394 324 297
length L = 1000 mm
Fan speed and mean air temperature tA
1 - min. speed 2 - med. speed 3 - max. speed
Mean water temperature tW 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C
90 °C 793 737 715 938 872 845 1 219 1 133 1 098
70 °C 570 515 493 674 609 583 876 791 758
60 °C 460 406 384 544 480 455 707 624 591
45 °C 299 246 225 353 291 266 459 378 346
length L = 1250 mm
Fan speed and mean air temperature tA
1 - min. speed 2 - med. speed 3 - max. speed
Mean water temperature tW 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C
90 °C 1 077 1 000 970 1 273 1 183 1 147 1 654 1 537 1 490
70 °C 774 699 669 915 827 791 1 189 1 074 1 028
60 °C 625 551 522 739 652 617 960 847 802
45 °C 406 334 306 480 395 361 623 513 470
length L = 1500 mm
Fan speed and mean air temperature tA
1 - min. speed 2 - med. speed 3 - max. speed
Mean water temperature tW 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C
90 °C 1 360 1 264 1 225 1 608 1 494 1 449 2 090 1 941 1 882
70 °C 977 883 845 1 156 1 044 1 000 1 502 1 357 1 299
60 °C 789 696 659 933 823 779 1 213 1 070 1 013
45 °C 512 422 386 606 499 457 787 648 593
length L = 1750 mm
Fan speed and mean air temperature tA
1 - min. speed 2 - med. speed 3 - max. speed
Mean water temperature tW 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C
90 °C 1 643 1 527 1 481 1 943 1 806 1 751 2 525 2 346 2 275
70 °C 1 181 1 067 1 022 1 397 1 262 1 208 1 814 1 639 1 569
60 °C 954 841 796 1 128 995 942 1 465 1 292 1 224
45 °C 619 510 466 732 603 552 951 783 717
length L = 2000 mm
Fan speed and mean air temperature tA
1 - min. speed 2 - med. speed 3 - max. speed
Mean water temperature tW 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C 15 °C 20 °C 22 °C
90 °C 1 927 1 790 1 736 2 279 2 117 2 053 2 960 2 750 2 667
70 °C 1 385 1 251 1 198 1 637 1 479 1 416 2 127 1 922 1 840
60 °C 1 118 986 934 1 322 1 166 1 104 1 718 1 515 1 435
45 °C 726 598 547 858 707 647 1 115 918 840

Search

News

Catalogue

New catalogue MINIB 2010/2011
Download our new catalogue for the year 2010/2011!



Video

Video

Assembly instructions
for floor convectors
play video »

Assembly instructions
for standing convectors
play video »


Management of quality

En-small

Since the year 2007 we have got the Certificate of Management of Quality for ISO 9001:2001 for the field of activity – manufacture of heating convectors.


EC Declaration of Conformity

Confirmity

All our listed products meet general requirements according to Statutory Rules no. 190/2002 Sb.