Su2

CROSS SECTION

Su2
Download-in-pdf-icon Download-reader-icon

COIL – SU2

  • self-standing floor convector with a width of only 116 mm
  • only for heating of dry environments
  • equipped with the thermostatic head.


DIMENSIONS

total width
116 mm
construction height
400 mm
length
900 - 2000 mm

USAGE

Convector SU2 is a fast reacting heating unit from a new design series of MINIB self-standing convectors without the fan. The aluminium cover of the unit can be supplied with silver, light bronze, dark bronze or white-varnished coating.

info:
The decorative grille of the convector must not be loaded.


TEMPERATURE EQUATION - HEATING

Q = μ QN
(
tW-tA 50
)
m
m = 1,3764 temperature exponent
tW, A mean water temperature, mean air temperature [°C]
QN nominal heat transfer rate for temperatures tW/tA 70/20 °C [W]
μ μ = 1 (select μ according to the diagram for other than flow nominal values)
Q heat transfer rate for other [W]

HEAT TRANSFER RATE - Q [W]

°C
°C
°C
°C
length L = 900 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 044 950 912
80 °C 858 768 733
70 °C 681 598 565
50 °C 366 296 269
length L = 1000 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 190 1 082 1 040
80 °C 977 876 836
70 °C 777 681 644
50 °C 417 337 307
length L = 1250 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 555 1 414 1 359
80 °C 1 277 1 144 1 092
70 °C 1 015 890 842
50 °C 545 441 401
length L = 1500 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 920 1 747 1 678
80 °C 1 577 1 413 1 348
70 °C 1 253 1 099 1 039
50 °C 673 544 495
length L = 1750 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 2 286 2 079 1 997
80 °C 1 877 1 681 1 605
70 °C 1 491 1 308 1 237
50 °C 801 648 589
length L = 2000 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 2 651 2 411 2 316
80 °C 2 177 1 950 1 861
70 °C 1 730 1 517 1 434
50 °C 929 751 683

Search

News

Catalogue

New catalogue MINIB 2009/2010
Download our new catalogue for the year 2009/2010!



Video

Video

Assembly instructions
for floor convectors
play video »

Assembly instructions
for standing convectors
play video »


Management of quality

En-small

Since the year 2007 we have got the Certificate of Management of Quality for ISO 9001:2001 for the field of activity – manufacture of heating convectors.


EC Declaration of Conformity

Confirmity

All our listed products meet general requirements according to Statutory Rules no. 190/2002 Sb.