Phone 220 180 780, E-mail: office@minib.cz
COIL – SU2
- self-standing floor convector with a width of only 116 mm
- only for heating of dry environments
- equipped with the thermostatic head.
DIMENSIONS
- total width
- 116 mm
- construction height
- 400 mm
- length
- 900 - 2000 mm
USAGE
Convector SU2 is a fast reacting heating unit from a new design series of MINIB self-standing convectors without the fan. The aluminium cover of the unit can be supplied with silver, light bronze, dark bronze or white-varnished coating.
info:
The decorative grille of the convector must not be loaded.
TEMPERATURE EQUATION - HEATING
| m = 1,3764 | temperature exponent |
|---|---|
| tW, A | mean water temperature, mean air temperature [°C] |
| QN | nominal heat transfer rate for temperatures tW/tA 70/20 °C [W] |
| μ | μ = 1 (select μ according to the diagram for other than flow nominal values) |
| Q | heat transfer rate for other [W] |
HEAT TRANSFER RATE Q [W]
| length L = 900 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 1 044 | 950 | 912 |
| 70 °C | 681 | 598 | 565 |
| 60 °C | 517 | 440 | 410 |
| 45 °C | 296 | 230 | 205 |
| length L = 1000 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 1 190 | 1 082 | 1 040 |
| 70 °C | 777 | 681 | 644 |
| 60 °C | 589 | 501 | 467 |
| 45 °C | 337 | 262 | 234 |
| length L = 1250 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 1 555 | 1 414 | 1 359 |
| 70 °C | 1 015 | 890 | 842 |
| 60 °C | 770 | 655 | 610 |
| 45 °C | 441 | 343 | 306 |
| length L = 1500 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 1 920 | 1 747 | 1 678 |
| 70 °C | 1 253 | 1 099 | 1 039 |
| 60 °C | 951 | 808 | 753 |
| 45 °C | 544 | 423 | 377 |
| length L = 1750 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 2 286 | 2 079 | 1 997 |
| 70 °C | 1 491 | 1 308 | 1 237 |
| 60 °C | 1 131 | 962 | 897 |
| 45 °C | 648 | 504 | 449 |
| length L = 2000 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 2 651 | 2 411 | 2 316 |
| 70 °C | 1 730 | 1 517 | 1 434 |
| 60 °C | 1 312 | 1 116 | 1 040 |
| 45 °C | 751 | 584 | 521 |
Search
Video
Assembly instructions
for floor convectors
play video »
Assembly instructions
for standing convectors
play video »
Management of quality
Since the year 2007 we have got the Certificate of Management of Quality for ISO 9001:2001 for the field of activity – manufacture of heating convectors.
EC Declaration of Conformity
All our listed products meet general requirements according to Statutory Rules no. 190/2002 Sb.