COIL – P
- for heating dry interiors
- lower heat output
- standard variant from P convector series
DIMENSIONS
- total width
- 243 mm
- construction height
- 125 mm
- length
- 900 - 3000 mm
USAGE
It is recommended to be combined with another heating system or to be used individually in interiors with lower heat demands. These convectors can be combined with the Coil – KT-3 with the 12V fan that has a significantly higher heat output at the same width.
TEMPERATURE EQUATION - HEATING
Q = μ QN
(
tW-tA
50
)
m
| m = 1,4633 | temperature exponent |
|---|---|
| tW, A | mean water temperature, mean air temperature [°C] |
| QN | nominal heat transfer rate for temperatures tW/tA 70/20 °C [W] |
| μ | μ = 1 (select μ according to the diagram for other than flow nominal values) |
| Q | heat transfer rate for other [W] |
HEAT TRANSFER RATE - Q [W]
| length L = 900 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 329 | 299 | 287 |
| 80 °C | 269 | 240 | 229 |
| 70 °C | 213 | 186 | 176 |
| 50 °C | 113 | 91 | 82 |
| length L = 1000 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 384 | 348 | 335 |
| 80 °C | 314 | 281 | 268 |
| 70 °C | 248 | 217 | 205 |
| 50 °C | 131 | 106 | 96 |
| length L = 1250 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 521 | 473 | 454 |
| 80 °C | 426 | 381 | 363 |
| 70 °C | 337 | 295 | 278 |
| 50 °C | 178 | 144 | 130 |
| length L = 1500 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 658 | 597 | 574 |
| 80 °C | 538 | 481 | 459 |
| 70 °C | 426 | 372 | 351 |
| 50 °C | 225 | 181 | 165 |
| length L = 1750 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 795 | 722 | 693 |
| 80 °C | 650 | 581 | 554 |
| 70 °C | 514 | 450 | 425 |
| 50 °C | 272 | 219 | 199 |
| length L = 2000 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 933 | 846 | 813 |
| 80 °C | 763 | 681 | 650 |
| 70 °C | 603 | 527 | 498 |
| 50 °C | 319 | 257 | 233 |
| length L = 2500 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 1 207 | 1 095 | 1 051 |
| 80 °C | 987 | 882 | 841 |
| 70 °C | 780 | 682 | 644 |
| 50 °C | 413 | 333 | 302 |
| length L = 3000 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 1 481 | 1 344 | 1 290 |
| 80 °C | 1 211 | 1 082 | 1 032 |
| 70 °C | 958 | 837 | 791 |
| 50 °C | 507 | 408 | 371 |
Search
Video
Assembly instructions
for floor convectors
play video »
Assembly instructions
for standing convectors
play video »
Management of quality
Since the year 2007 we have got the Certificate of Management of Quality for ISO 9001:2001 for the field of activity – manufacture of heating convectors.
EC Declaration of Conformity
All our listed products meet general requirements according to Statutory Rules no. 190/2002 Sb.