Pmw165

CROSS SECTION

Pmw165

LONGITUDINAL SECTION

Pmw165
Download-in-pdf-icon Download-reader-icon

COIL – PMW165

  • for heating dry interiors
  • high heat output without fan

DIMENSIONS

total width
420 mm
construction height
165 mm
length
900 - 3000 mm

USAGE

It is recommended for individual use in dry interiors with demand on higher heat output where the construction height is not a limiting factor.


TEMPERATURE EQUATION - HEATING

Q = μ QN
(
tW-tA 50
)
m
m = 1,3854 temperature exponent
tW, A mean water temperature, mean air temperature [°C]
QN nominal heat transfer rate for temperatures tW/tA 70/20 °C [W]
μ μ = 1 (select μ according to the diagram for other than flow nominal values)
Q heat transfer rate for other [W]

HEAT TRANSFER RATE Q [W]

°C
°C
°C
°C
length L = 900 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 937 850 815
70 °C 604 528 498
60 °C 455 385 358
45 °C 257 198 176
length L = 1000 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 093 991 951
70 °C 705 616 582
60 °C 531 449 418
45 °C 299 231 206
length L = 1250 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 483 1 345 1 291
70 °C 957 836 789
60 °C 720 610 567
45 °C 406 314 279
length L = 1500 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 873 1 699 1 631
70 °C 1 208 1 056 997
60 °C 910 771 717
45 °C 513 397 353
length L = 1750 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 2 263 2 053 1 971
70 °C 1 460 1 276 1 205
60 °C 1 100 931 866
45 °C 620 479 426
length L = 2000 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 2 654 2 407 2 311
70 °C 1 712 1 496 1 412
60 °C 1 289 1 092 1 015
45 °C 727 562 499
length L = 2500 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 3 434 3 115 2 990
70 °C 2 216 1 936 1 828
60 °C 1 669 1 413 1 314
45 °C 941 727 646
length L = 3000 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 4 215 3 823 3 670
70 °C 2 719 2 376 2 243
60 °C 2 048 1 734 1 613
45 °C 1 155 892 793

Search

News

Catalogue

New catalogue MINIB 2010/2011
Download our new catalogue for the year 2010/2011!



Video

Video

Assembly instructions
for floor convectors
play video »

Assembly instructions
for standing convectors
play video »


Management of quality

En-small

Since the year 2007 we have got the Certificate of Management of Quality for ISO 9001:2001 for the field of activity – manufacture of heating convectors.


EC Declaration of Conformity

Confirmity

All our listed products meet general requirements according to Statutory Rules no. 190/2002 Sb.