Pmw165

CROSS SECTION

Pmw165

LONGITUDINAL SECTION

Pmw165
Download-in-pdf-icon Download-reader-icon

COIL – PMW165

  • for heating dry interiors
  • high heat output without fan

DIMENSIONS

total width
420 mm
construction height
165 mm
length
900 - 3000 mm

USAGE

It is recommended for individual use in dry interiors with demand on higher heat output where the construction height is not a limiting factor.


TEMPERATURE EQUATION - HEATING

Q = μ QN
(
tW-tA 50
)
m
m = 1,3854 temperature exponent
tW, A mean water temperature, mean air temperature [°C]
QN nominal heat transfer rate for temperatures tW/tA 70/20 °C [W]
μ μ = 1 (select μ according to the diagram for other than flow nominal values)
Q heat transfer rate for other [W]

HEAT TRANSFER RATE - Q [W]

°C
°C
°C
°C
length L = 900 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 823 748 718
80 °C 675 604 576
70 °C 535 469 443
50 °C 286 231 210
length L = 1000 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 960 873 838
80 °C 787 705 672
70 °C 625 547 517
50 °C 334 270 245
length L = 1250 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 303 1 184 1 137
80 °C 1 069 956 913
70 °C 848 743 702
50 °C 453 366 333
length L = 1500 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 646 1 496 1 437
80 °C 1 350 1 208 1 153
70 °C 1 071 938 887
50 °C 573 462 420
length L = 1750 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 989 1 807 1 736
80 °C 1 631 1 460 1 393
70 °C 1 294 1 134 1 072
50 °C 692 559 508
length L = 2000 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 2 331 2 119 2 036
80 °C 1 912 1 711 1 633
70 °C 1 517 1 329 1 256
50 °C 811 655 595
length L = 2500 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 3 017 2 742 2 634
80 °C 2 475 2 215 2 113
70 °C 1 963 1 720 1 626
50 °C 1 050 848 771
length L = 3000 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 3 703 3 365 3 233
80 °C 3 037 2 718 2 594
70 °C 2 410 2 111 1 995
50 °C 1 288 1 040 946

Search

News

Catalogue

New catalogue MINIB 2009/2010
Download our new catalogue for the year 2009/2010!



Video

Video

Assembly instructions
for floor convectors
play video »

Assembly instructions
for standing convectors
play video »


Management of quality

En-small

Since the year 2007 we have got the Certificate of Management of Quality for ISO 9001:2001 for the field of activity – manufacture of heating convectors.


EC Declaration of Conformity

Confirmity

All our listed products meet general requirements according to Statutory Rules no. 190/2002 Sb.