Pmw205

CROSS SECTION

Pmw205

LONGITUDINAL SECTION

Pmw205
Download-in-pdf-icon Download-reader-icon

COIL – PMW205

  • for heating dry interiors
  • high heat output without fan

DIMENSIONS

total width
420 mm
construction height
205 mm
length
900 - 3000 mm

USAGE

It is recommended for individual use in dry interiors with demand on higher heat output where the construction height is not a limiting factor.


TEMPERATURE EQUATION - HEATING

Q = μ QN
(
tW-tA 50
)
m
m = 1,4236 temperature exponent
tW, A mean water temperature, mean air temperature [°C]
QN nominal heat transfer rate for temperatures tW/tA 70/20 °C [W]
μ μ = 1 (select μ according to the diagram for other than flow nominal values)
Q heat transfer rate for other [W]

HEAT TRANSFER RATE - Q [W]

°C
°C
°C
°C
length L = 900 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 961 871 836
80 °C 784 699 667
70 °C 618 540 509
50 °C 325 261 236
length L = 1000 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 121 1 016 975
80 °C 915 816 778
70 °C 721 630 594
50 °C 379 304 276
length L = 1250 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 522 1 379 1 324
80 °C 1 241 1 107 1 055
70 °C 978 854 806
50 °C 514 413 374
length L = 1500 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 922 1 742 1 672
80 °C 1 568 1 399 1 333
70 °C 1 236 1 079 1 018
50 °C 649 522 473
length L = 1750 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 2 322 2 105 2 020
80 °C 1 894 1 690 1 611
70 °C 1 493 1 304 1 230
50 °C 785 630 571
length L = 2000 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 2 723 2 468 2 368
80 °C 2 221 1 982 1 888
70 °C 1 751 1 529 1 442
50 °C 920 739 670
length L = 2500 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 3 524 3 194 3 065
80 °C 2 874 2 565 2 444
70 °C 2 266 1 978 1 867
50 °C 1 191 956 867
length L = 3000 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 4 325 3 920 3 762
80 °C 3 528 3 148 2 999
70 °C 2 781 2 428 2 291
50 °C 1 461 1 173 1 064

Search

News

Catalogue

New catalogue MINIB 2009/2010
Download our new catalogue for the year 2009/2010!



Video

Video

Assembly instructions
for floor convectors
play video »

Assembly instructions
for standing convectors
play video »


Management of quality

En-small

Since the year 2007 we have got the Certificate of Management of Quality for ISO 9001:2001 for the field of activity – manufacture of heating convectors.


EC Declaration of Conformity

Confirmity

All our listed products meet general requirements according to Statutory Rules no. 190/2002 Sb.