Pmw90

CROSS SECTION

Pmw90

LONGITUDINAL SECTION

Pmw90
Download-in-pdf-icon Download-reader-icon

COIL – PMW90

  • for heating dry interiors
  • high heat output without fan
  • construction height only 90 mm

DIMENSIONS

total width
420 mm
construction height
90 mm
length
900 - 3000 mm

USAGE

It is recommended for individual use in dry interiors with medium heat demands in places where the construction height is not a limiting factor.


TEMPERATURE EQUATION - HEATING

Q = μ QN
(
tW-tA 50
)
m
m = 1,3577 temperature exponent
tW, A mean water temperature, mean air temperature [°C]
QN nominal heat transfer rate for temperatures tW/tA 70/20 °C [W]
μ μ = 1 (select μ according to the diagram for other than flow nominal values)
Q heat transfer rate for other [W]

HEAT TRANSFER RATE - Q [W]

°C
°C
°C
°C
length L = 900 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 521 475 456
80 °C 429 385 368
70 °C 342 301 284
50 °C 185 150 137
length L = 1000 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 608 554 533
80 °C 501 449 429
70 °C 399 351 332
50 °C 216 175 160
length L = 1250 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 826 752 723
80 °C 680 610 582
70 °C 542 476 450
50 °C 293 238 217
length L = 1500 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 043 950 913
80 °C 859 770 736
70 °C 684 601 569
50 °C 371 301 274
length L = 1750 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 260 1 147 1 103
80 °C 1 038 931 889
70 °C 827 727 687
50 °C 448 363 331
length L = 2000 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 477 1 345 1 293
80 °C 1 216 1 091 1 042
70 °C 970 852 806
50 °C 525 426 388
length L = 2500 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 912 1 741 1 674
80 °C 1 574 1 412 1 349
70 °C 1 255 1 102 1 043
50 °C 679 551 502
length L = 3000 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 2 346 2 136 2 054
80 °C 1 932 1 733 1 655
70 °C 1 540 1 353 1 280
50 °C 834 676 616

Search

News

Catalogue

New catalogue MINIB 2009/2010
Download our new catalogue for the year 2009/2010!



Video

Video

Assembly instructions
for floor convectors
play video »

Assembly instructions
for standing convectors
play video »


Management of quality

En-small

Since the year 2007 we have got the Certificate of Management of Quality for ISO 9001:2001 for the field of activity – manufacture of heating convectors.


EC Declaration of Conformity

Confirmity

All our listed products meet general requirements according to Statutory Rules no. 190/2002 Sb.