Pmw90

CROSS SECTION

Pmw90

LONGITUDINAL SECTION

Pmw90
Download-in-pdf-icon Download-reader-icon

COIL – PMW90

  • for heating dry interiors
  • high heat output without fan
  • construction height only 90 mm

DIMENSIONS

total width
420 mm
construction height
90 mm
length
900 - 3000 mm

USAGE

It is recommended for individual use in dry interiors with medium heat demands in places where the construction height is not a limiting factor.


TEMPERATURE EQUATION - HEATING

Q = μ QN
(
tW-tA 50
)
m
m = 1,3577 temperature exponent
tW, A mean water temperature, mean air temperature [°C]
QN nominal heat transfer rate for temperatures tW/tA 70/20 °C [W]
μ μ = 1 (select μ according to the diagram for other than flow nominal values)
Q heat transfer rate for other [W]

HEAT TRANSFER RATE Q [W]

°C
°C
°C
°C
length L = 900 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 466 422 405
70 °C 299 260 245
60 °C 224 189 175
45 °C 125 96 85
length L = 1000 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 544 493 473
70 °C 348 304 286
60 °C 261 220 205
45 °C 146 112 99
length L = 1250 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 738 669 641
70 °C 473 412 389
60 °C 354 299 278
45 °C 198 152 135
length L = 1500 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 933 845 810
70 °C 597 521 491
60 °C 447 378 351
45 °C 250 192 170
length L = 1750 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 127 1 021 979
70 °C 721 629 593
60 °C 540 456 424
45 °C 302 232 206
length L = 2000 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 321 1 197 1 148
70 °C 846 737 695
60 °C 634 535 497
45 °C 354 272 241
length L = 2500 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 710 1 549 1 485
70 °C 1 095 954 900
60 °C 820 692 643
45 °C 458 352 312
length L = 3000 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 2 099 1 900 1 823
70 °C 1 343 1 171 1 104
60 °C 1 006 849 789
45 °C 562 432 383

Search

News

Catalogue

New catalogue MINIB 2010/2011
Download our new catalogue for the year 2010/2011!



Video

Video

Assembly instructions
for floor convectors
play video »