Strešovická 49, 162 00 Praha 6
Phone 220 180 780, E-mail: office@minib.cz
Phone 220 180 780, E-mail: office@minib.cz
COIL – PT/4
- for heating dry interiors
- identical in dimension to convectors PT, PO but
- it has a higher output Q
- supplied with thermostatic head as standard
DIMENSIONS
- total width
- 303 mm
- construction height
- 125 mm
- length
- 900 - 3000 mm
USAGE
COIL PT/4 is recommended for individual use in interiors where COIL PT does not efficiently cover the heat requirement. COIL PT/4 can be also combined with COIL KT or MT, which have a significantly higher heat output.
TEMPERATURE EQUATION - HEATING
Q = μ QN
(
tW-tA
50
)
m
| m = 1,466748 | temperature exponent |
|---|---|
| tW, A | mean water temperature, mean air temperature [°C] |
| QN | nominal heat transfer rate for temperatures tW/tA 70/20 °C [W] |
| μ | μ = 1 (select μ according to the diagram for other than flow nominal values) |
| Q | heat transfer rate for other [W] |
HEAT TRANSFER RATE - Q [W]
| length L = 900 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 514 | 464 | 445 |
| 80 °C | 416 | 370 | 352 |
| 70 °C | 326 | 283 | 267 |
| 50 °C | 168 | 134 | 121 |
| length L = 1000 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 599 | 542 | 519 |
| 80 °C | 486 | 432 | 411 |
| 70 °C | 380 | 331 | 311 |
| 50 °C | 196 | 156 | 141 |
| length L = 1250 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 813 | 735 | 704 |
| 80 °C | 659 | 586 | 558 |
| 70 °C | 516 | 449 | 423 |
| 50 °C | 266 | 212 | 192 |
| length L = 1500 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 1 027 | 929 | 890 |
| 80 °C | 833 | 741 | 705 |
| 70 °C | 652 | 567 | 534 |
| 50 °C | 336 | 268 | 242 |
| length L = 1750 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 1 241 | 1 122 | 1 075 |
| 80 °C | 1 006 | 895 | 852 |
| 70 °C | 788 | 685 | 645 |
| 50 °C | 406 | 324 | 293 |
| length L = 2000 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 1 455 | 1 315 | 1 261 |
| 80 °C | 1 180 | 1 049 | 998 |
| 70 °C | 924 | 803 | 756 |
| 50 °C | 476 | 380 | 343 |
| length L = 2500 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 1 884 | 1 702 | 1 631 |
| 80 °C | 1 527 | 1 358 | 1 292 |
| 70 °C | 1 195 | 1 039 | 979 |
| 50 °C | 616 | 491 | 444 |
| length L = 3000 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 2 312 | 2 089 | 2 002 |
| 80 °C | 1 874 | 1 666 | 1 586 |
| 70 °C | 1 467 | 1 275 | 1 201 |
| 50 °C | 756 | 603 | 545 |
Search
Video
Assembly instructions
for floor convectors
play video »
Assembly instructions
for standing convectors
play video »
Management of quality
Since the year 2007 we have got the Certificate of Management of Quality for ISO 9001:2001 for the field of activity – manufacture of heating convectors.
EC Declaration of Conformity
All our listed products meet general requirements according to Statutory Rules no. 190/2002 Sb.