Strešovická 49, 162 00 Praha 6
Phone 220 180 780, E-mail: office@minib.cz
Phone 220 180 780, E-mail: office@minib.cz
COIL – PT/4
- for heating dry interiors
- identical in dimension to convectors PT, PO but it has a higher output Q
- supplied with thermostatic head as standard
DIMENSIONS
- total width
- 303 mm
- construction height
- 125 mm
- length
- 900 - 3000 mm
USAGE
COIL PT/4 is recommended for individual use in interiors where COIL PT does not efficiently cover the heat requirement. COIL PT/4 can be also combined with COIL KT and MT, which have a significantly higher heat output.
TEMPERATURE EQUATION - HEATING
Q = μ QN
(
tW-tA
50
)
m
| m = 1,466748 | temperature exponent |
|---|---|
| tW, A | mean water temperature, mean air temperature [°C] |
| QN | nominal heat transfer rate for temperatures tW/tA 70/20 °C [W] |
| μ | μ = 1 (select μ according to the diagram for other than flow nominal values) |
| Q | heat transfer rate for other [W] |
HEAT TRANSFER RATE Q [W]
| length L = 900 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 553 | 500 | 480 |
| 70 °C | 353 | 307 | 289 |
| 60 °C | 263 | 222 | 206 |
| 45 °C | 146 | 112 | 99 |
| length L = 1000 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 645 | 584 | 560 |
| 70 °C | 411 | 358 | 338 |
| 60 °C | 307 | 259 | 240 |
| 45 °C | 171 | 131 | 116 |
| length L = 1250 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 876 | 792 | 760 |
| 70 °C | 558 | 486 | 458 |
| 60 °C | 417 | 352 | 326 |
| 45 °C | 232 | 178 | 157 |
| length L = 1500 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 1 106 | 1 001 | 960 |
| 70 °C | 705 | 614 | 579 |
| 60 °C | 527 | 444 | 412 |
| 45 °C | 293 | 224 | 199 |
| length L = 1750 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 1 337 | 1 209 | 1 160 |
| 70 °C | 852 | 742 | 699 |
| 60 °C | 637 | 537 | 498 |
| 45 °C | 353 | 271 | 240 |
| length L = 2000 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 1 567 | 1 418 | 1 360 |
| 70 °C | 999 | 870 | 820 |
| 60 °C | 747 | 629 | 584 |
| 45 °C | 414 | 318 | 282 |
| length L = 2500 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 2 028 | 1 835 | 1 759 |
| 70 °C | 1 293 | 1 126 | 1 061 |
| 60 °C | 966 | 814 | 756 |
| 45 °C | 536 | 412 | 365 |
| length L = 3000 mm | |||
|---|---|---|---|
| Mean air temperature tA | |||
| Mean water temperature tW | 15 °C | 20 °C | 22 °C |
| 90 °C | 2 489 | 2 252 | 2 159 |
| 70 °C | 1 587 | 1 382 | 1 302 |
| 60 °C | 1 186 | 999 | 928 |
| 45 °C | 658 | 505 | 447 |
Search
Video
Assembly instructions
for floor convectors
play video »
Assembly instructions
for standing convectors
play video »
Management of quality
Since the year 2007 we have got the Certificate of Management of Quality for ISO 9001:2001 for the field of activity – manufacture of heating convectors.
EC Declaration of Conformity
All our listed products meet general requirements according to Statutory Rules no. 190/2002 Sb.