Coil-pw

CROSS SECTION

Coil-pw-cross_section

LONGITUDINAL SECTION

Coil-pw-longitudinal_sectio
Download-in-pdf-icon Download-reader-icon

COIL – PW

  • high heat output convector without fan 

DIMENSIONS

total width
380 mm
construction height
125 mm
length
900 - 3000 mm

USAGE

Designed to provide medium heat output where construction width is not a limiting factor. 


TEMPERATURE EQUATION - HEATING

Q = μ QN
(
tW-tA 50
)
m
m = 1,421162 temperature exponent
tW, A mean water temperature, mean air temperature [°C]
QN nominal heat transfer rate for temperatures tW/tA 70/20 °C [W]
μ μ = 1 (select μ according to the diagram for other than flow nominal values)
Q heat transfer rate for other [W]

HEAT TRANSFER RATE Q [W]

°C
°C
°C
°C
length L = 900 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 509 462 443
70 °C 328 286 270
60 °C 246 208 194
45 °C 138 107 95
length L = 1000 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 594 539 517
70 °C 382 334 315
60 °C 287 243 226
45 °C 162 125 111
length L = 1250 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 806 731 701
70 °C 519 453 428
60 °C 390 330 307
45 °C 219 169 150
length L = 1500 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 018 923 886
70 °C 655 572 540
60 °C 493 417 387
45 °C 277 214 190
length L = 1750 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 230 1 116 1 070
70 °C 792 692 653
60 °C 595 504 468
45 °C 335 258 229
length L = 2000 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 443 1 308 1 255
70 °C 928 811 765
60 °C 698 590 549
45 °C 392 303 269
length L = 2500 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 867 1 693 1 624
70 °C 1 201 1 049 990
60 °C 903 764 710
45 °C 508 392 348
length L = 3000 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 2 291 2 077 1 993
70 °C 1 474 1 288 1 215
60 °C 1 109 938 872
45 °C 623 481 427

Search

News

Catalogue

New catalogue MINIB 2010/2011
Download our new catalogue for the year 2010/2011!



Video

Video

Assembly instructions
for floor convectors
play video »