Coil-pw

CROSS SECTION

Coil-pw-cross_section

LONGITUDINAL SECTION

Coil-pw-longitudinal_sectio
Download-in-pdf-icon Download-reader-icon

COIL – PW

  • high heat output convector without fan 

DIMENSIONS

total width
380 mm
construction height
125 mm
length
900 - 3000 mm

USAGE

Designed to provide medium heat output where construction width is not a limiting factor. 


TEMPERATURE EQUATION - HEATING

Q = μ QN
(
tW-tA 50
)
m
m = 1,421162 temperature exponent
tW, A mean water temperature, mean air temperature [°C]
QN nominal heat transfer rate for temperatures tW/tA 70/20 °C [W]
μ μ = 1 (select μ according to the diagram for other than flow nominal values)
Q heat transfer rate for other [W]

HEAT TRANSFER RATE - Q [W]

°C
°C
°C
°C
length L = 900 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 509 462 443
80 °C 415 371 353
70 °C 328 286 270
50 °C 172 138 126
length L = 1000 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 594 539 517
80 °C 485 433 412
70 °C 382 334 315
50 °C 201 162 146
length L = 1250 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 806 731 701
80 °C 658 587 559
70 °C 519 453 428
50 °C 273 219 199
length L = 1500 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 018 923 886
80 °C 831 742 707
70 °C 655 572 540
50 °C 345 277 251
length L = 1750 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 230 1 116 1 070
80 °C 1 004 896 854
70 °C 792 692 653
50 °C 417 335 303
length L = 2000 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 443 1 308 1 255
80 °C 1 177 1 051 1 001
70 °C 928 811 765
50 °C 488 392 356
length L = 2500 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 1 867 1 693 1 624
80 °C 1 523 1 360 1 296
70 °C 1 201 1 049 990
50 °C 632 508 460
length L = 3000 mm
Mean air temperature tA
Mean water temperature tW 15 °C 20 °C 22 °C
90 °C 2 291 2 077 1 993
80 °C 1 870 1 669 1 590
70 °C 1 474 1 288 1 215
50 °C 776 623 565

Search

News

Catalogue

New catalogue MINIB 2009/2010
Download our new catalogue for the year 2009/2010!



Video

Video

Assembly instructions
for floor convectors
play video »

Assembly instructions
for standing convectors
play video »


Management of quality

En-small

Since the year 2007 we have got the Certificate of Management of Quality for ISO 9001:2001 for the field of activity – manufacture of heating convectors.


EC Declaration of Conformity

Confirmity

All our listed products meet general requirements according to Statutory Rules no. 190/2002 Sb.