Physical characteristics of MINIB convectors

Acoustic pressure

COIL-KT/KO, COIL-MT/MO, KT-2/KO-2, HC-4P, MT-2

Graph-1-small

COIL-T50

Graph-2-small

Experimental values for acoustic pressure levels associated with Minib convectors are shown on this page. Results are based on a sound pressure measurement taken at 1m from the outlet of the convector at an angle of 45° from the floor. The convectors were embedded in concrete in an acoustically hard room. If installed in a furnished and carpeted area it would be expected that the sound pressure levels would be 1 to 2 dB lower than those shown due to increased room absorption. For the purposes of comparison, a personal computer in the room used for the measurements gave a sound pressure level of 40.8 dB.
The results are shown individually for the different types of convector and fan diameters available. For all lengths and types of convector speed 1 & 2 give very low sound pressure levels and are suitable for both daytime and night time operation. We recommend that convectors are selected based on medium speed but for applications where noise levels must be minimised or there are a large number of units then minimum speed may be used.

COIL-KT-0

Graph-3-small

COIL-KT-3, HC, SK-1, NK-2, SK, KP

Graph-4-small

COIL-KT-1

Graph-5-small

COIL-T80

Graf-t80-small

Approximate air flow of MINIB convectors MINIB, m3/h

fan wheel diameter convector length min. speed med. speed max. speed
30 mm 1000 mm 100 120 250
50 mm 1000 mm 200 220 300

Info:
Airflow values listed in the table are valid for convector length of 1000 mm. For other lengths, multiply these unit flows by the relevant length of the convector in metres (e.g. COIL-KT at a length of 2 500mm has a flow 220 x 2.5 = 550 m3/ hour for medium speed).


Water volume of MINIB convectors, dm3

Length of the convector, m 0,9 1,0 1,25 1,5 1,75 2,0 2,5 3,0
Heat exchanger water volume, dm3
(for the pipe diameter 15 mm)
0,2 0,25 0,3 0,4 0,5 0,6 0,7 0,9
Heat exchanger water volume, dm3
(for the pipe diameter 12 mm)
0,13 0,15 0,2 0,25 0,3 0,35 0,4 0,5

Pressure losses of MINIB convectors

(including the effect of the screwed fitting and manual shut-off valve)

for all lenghts of heat exchangers

Pressure-looses

Characteristics of the thermostatic head

Thermostatic-characteristic
  1. Setting of the minimum temperature, opening of the thermostatic head
  2. Setting of the maximum temperature, opening of the thermostatic head
  3. Setting of the mean temperature, opening of the thermostatic head
  4. Setting of the mean temperature, closing of the thermostatic head
  5. Setting of the mean temperature. Pressure difference is 60kPa when the thermostatic head is closed

Characteristics of the screwed fitting

(for MINIB convectors)

Flow diagram of control valve (Kv values)

Regulation-characteristic
setting (turns) 0,5 1 1,5 2 2,5 3 3,5 4 4,5 5 5,5 5,75
Kv [m3.h-1] 0 0,09 0,18 0,37 0,54 0,72 0,93 1,13 1,23 1,31 1,35 1,38

Example of necessary adjustment of fittings:

Set:
Flow Q=180kg/h
Requirement:
Setting for differential pressure p=10 000 Pa
Solution:
Required setting is the intersection of values drawn on axes of the flow and pressure loss.
The result is the setting by 2.5 turns.

Search

News

Catalogue

New catalogue MINIB 2010/2011
Download our new catalogue for the year 2010/2011!



Video

Video

Assembly instructions
for floor convectors
play video »

Assembly instructions
for standing convectors
play video »


Management of quality

En-small

Since the year 2007 we have got the Certificate of Management of Quality for ISO 9001:2001 for the field of activity – manufacture of heating convectors.


EC Declaration of Conformity

Confirmity

All our listed products meet general requirements according to Statutory Rules no. 190/2002 Sb.